1. intro
important modbus references:
-
30845 soc
-
30852 battery voltage
-
40149 charge
-
40151 activate mode
![]() |
increment the reference by 1 if using modpoll |
2. install modpoll
3. get battery voltage
modpoll -a 3 -r 30852 -c 2 -1 192.168.0.41
///
[30852]: 0
[30853]: 20929
4. get the soc
modpoll -a 3 -r 30846 -c 2 -1 192.168.0.41
///
[30846]: 0
[30847]: 10
5. set the soc
modpoll -a 3 -r 30846 192.168.0.41 0 12
Written 2 references.
6. turn on the write modus
modpoll -a 3 -r 40152 192.168.0.41 0 802
7. charge
10A
modpoll -a 3 -r 40150 192.168.0.41 65535 63535
20A
modpoll -a 3 -r 40150 192.168.0.41 65535 61535
30A
modpoll -a 3 -r 40150 192.168.0.41 65535 57535
8. turn off the write modus
modpoll -a 3 -r 40152 192.168.0.41 0 803